Ürünlerimiz
MultiCon CMC-141
Sipariş için Ürün Kodlama
MultiCon CMC-141

Power supply19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Power consumptiontypical 25 VA; max. 35 VA
Outputs 24 analog (4-20 mA) or 36 relay (1A/250V) / 72 SSR outputs or 18 relay 5A/250V max., sensor supply: 24 V DC ± 5% (200 mA max. for current inputs)
Measurement rangedepends on input
Display 5.7 inch graphic TFT, 16-bit colour, 320 x 240 pixels, with touch screen
Inputsup to 15 universal inputs; 72 analogue inputs (0/4-20 mA or 0/1-5V or 0/2-10V) max.; 72 digital inputs max.; 36 thermocouple inputs max.; 18 RTD inputs max.; 12 counter/ flowmeter/ ratemeter inputs max.; 1 digital input 24V DC (available in standard, integrated with  PS3 or PS4 power supply module)
Communication interface standard: RS-485 (Modbus RTU), 1 x USB Host; ETU version: 1 or 2 x USB Host, 1 x Ethernet 10 MB; enhanced ACM version: 2 x RS-485, 1 x RS-485/232, 1 or 2 x USB Host, 1 x Ethernet 10 MB
Available data recording speedfrom 0,1 s to 24 h with resolution 0,1 s
Internal memory capacity1,5 GB
Operating temperature0°C ÷ +50°C (optional -20°C ÷ +50°C with PCB conformal coating)
Storage temperature-10°C ÷ +70°C (optional -20°C ÷ +70°C with PCB conformal coating)
Case materialNORYL - GFN2S E1
 Case dimensions 144 x 144 x 100 mm
Casepanel mounting
Protection classIP 65 (front), available options: additional frame IP 65 for panel cut-out sealing, transparent door STD-141; version with front USB: IP 40 or IP 54 (when fitted with STD-141 transparent door)
Panel cut-out dimensions137 x 137 mm
Software Free DAQ Manager software for multichannel controller can be downloaded directly from section „Download”
Installation depthmin. 102 mm